Dashboard / Checks / CHK-2026-0182

Monthly Generator Test Run

Failed
Completed check records are immutable. To raise issues found here, create or update a corrective action.
Space / Procedure
SOP-GEN-001 · v3
Performed
Jake T.
13 May 09:14 → 09:42 · 28 min
Schedule
Due 10 May (overdue 3d at run)
Next due: 13 June

Item Results

7 pass · 1 fail
  • Oil level correct? Pass
  • No visible leaks? Pass
  • Coolant / water level correct? Fail · Critical
    Coolant level visibly below MIN line. Slight residue around radiator cap suggests recent loss.
    IMG_4231
  • Hours reading recorded? 1247 hrs
  • Battery condition acceptable? Pass
  • Generator started successfully? Yes
  • Generator ran for required duration? Yes · 17 min
  • Abnormal noise or smoke observed? No

Overall Notes

Coolant top-up applied during test as temporary measure. Pending root-cause investigation — see linked action.