Actions / CA-2026-0042

Investigate low coolant level

Urgent In progress

Description

Coolant level visibly below MIN line on Perkins 60kVA. Slight residue around radiator cap suggests recent loss. Top-up applied temporarily but root cause unclear — could be cap seal, hose, or radiator leak. Needs full inspection before next scheduled load test.

Maintenance Issue Link

Issue #1247 · Generator coolant leak investigation
Open · assigned to Maintenance · raised from this action 13 May
View in Maintenance →

Activity

  • JT
    Jake T. today 11:14
    Pressure-tested system, found weeping at radiator cap. Replacement cap ordered from supplier. ETA Friday.
  • System today 10:02
    Maintenance Issue #1247 created and linked.
  • System 13 May 09:42
    Action auto-raised from failed check item "Coolant / water level correct?" in Monthly Generator Test (CHK-2026-0182).

Details

Priority
Urgent
Status
In progress
Space
GEN-01
Assigned to
Jake T.
Department
Maintenance
Raised by
Jake T.
Raised
13 May 09:42
Due
Today

Attachments

IMG
IMG_4231.jpg
From check · 13 May
IMG
cap_residue.jpg
Added by Jake T. · today